SPEC 45001
1/C CU 600 or 1000V XLPE-SIM XHHW-2 Power Cable. CT Rated 1/0 and Larger
Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) with Simpull technology insulation XHHW-2. FT4/IEEE 1202 350kcmil and larger.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) with Simpull technology Type XHHW-2
Applications and Features:
Southwire’s 600 or 1000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. FT4/IEEE 1202 on 350kcmil and larger. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} SIMpull XHHW-2{R} E30117 MASTER-DESIGN {UL} XXX AWG(XXX{mm2}) CU TYPE XHHW-2 SUN. RES. FOR CT USE GASOLINE AND OIL RESISTANT II 600V/1000V {NOM}-ANCE LS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
113001◊ | 1/0 | 19 | 0.360 | 55 | 0.470 | 326 | 361 |
113019◊ | 2/0 | 19 | 0.404 | 55 | 0.514 | 411 | 450 |
113027◊ | 3/0 | 19 | 0.454 | 55 | 0.564 | 518 | 562 |
113035◊ | 4/0 | 19 | 0.510 | 55 | 0.620 | 653 | 703 |
113043◊ | 250 | 37 | 0.558 | 65 | 0.688 | 772 | 832 |
113050 | 300 | 37 | 0.611 | 65 | 0.741 | 926 | 991 |
113068◊ | 350 | 37 | 0.661 | 65 | 0.791 | 1081 | 1151 |
TBA | 400 | 37 | 0.706 | 65 | 0.835 | 1235 | 1316 |
113084◊ | 500 | 37 | 0.789 | 65 | 0.919 | 1544 | 1627 |
113092◊ | 600 | 61 | 0.866 | 80 | 1.026 | 1853 | 1960 |
113100◊ | 750 | 61 | 0.968 | 80 | 1.128 | 2316 | 2435 |
113134◊ | 1000 | 61 | 1.117 | 80 | 1.277 | 3088 | 3223 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
113001◊ | 1/0 | 1.9 | 845 | 0.102 | 0.128 | 0.028 | 125 | 150 | 170 |
113019◊ | 2/0 | 2.1 | 1065 | 0.081 | 0.102 | 0.027 | 145 | 175 | 195 |
113027◊ | 3/0 | 2.3 | 1342 | 0.064 | 0.081 | 0.027 | 165 | 200 | 225 |
113035◊ | 4/0 | 2.5 | 1693 | 0.051 | 0.064 | 0.026 | 195 | 230 | 260 |
113043◊ | 250 | 2.8 | 2000 | 0.043 | 0.055 | 0.027 | 215 | 255 | 290 |
113050 | 300 | 3.0 | 2400 | 0.036 | 0.046 | 0.026 | 240 | 285 | 320 |
113068◊ | 350 | 3.2 | 2800 | 0.031 | 0.040 | 0.026 | 260 | 310 | 350 |
TBA | 400 | 3.3 | 3200 | 0.026 | 0.035 | 0.025 | 280 | 335 | 380 |
113084◊ | 500 | 3.7 | 4000 | 0.022 | 0.029 | 0.025 | 320 | 380 | 430 |
113092◊ | 600 | 5.1 | 4800 | 0.018 | 0.024 | 0.026 | 350 | 420 | 475 |
113100◊ | 750 | 5.6 | 6000 | 0.014 | 0.020 | 0.025 | 400 | 475 | 535 |
113134◊ | 1000 | 6.4 | 8000 | 0.011 | 0.017 | 0.025 | 455 | 545 | 615 |
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00C