SPEC 45003

1/C CU 600V XLPE RHH/RHW-2 USE-2 Silicone-Free Power Cable

Power Cable 600Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2 CT Rated

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2 Silicone-Free

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • VW-1 (Vertical-Wire) Flame Test
  • PR I/II Oil Resistant
  • -40ºC Rated
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 {UL} XXX AWG (XX.X{mm2}) CU TYPE USE-2 OR RHH OR RHW-2 XX MILS XLP FOR CT USE SUN. RES. VW-1 600 VOLTS {NOM}-ANCE RHH/RHW-2 600V 90C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    8907001470.071450.1611220
    1134311270.089450.1792028
    1134491070.113450.2033242
    113456870.142600.2599567
    618689670.178600.30481109
    113472470.225600.345128153
    955872270.283600.403205244
    1135061190.322800.481258304
    8901051/0190.362800.522325390
    8901062/0190.405800.564410481
    8906313/0190.456800.616518598
    8901074/0190.512800.672653742
    890632250370.558950.748771884
    113563300370.611950.8019261023
    890108350370.661950.85110811213
    113589400370.706950.89612351345
    890109500370.789950.95615441696
    TBA600610.8661101.08518532028
    890633750610.9681101.18823162534
    1136471000611.1171101.33730883283
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    890700140.6322.5803.1700.024152025
    113431120.7521.6302.0000.021202530
    113449100.8831.0201.2500.019303540
    11345681.01320.6400.7860.019405055
    61868961.22090.4030.4950.018556575
    11347241.33330.2530.3100.015708595
    95587221.65300.1590.1950.01395115130
    11350611.96690.1260.1540.014110130145
    8901051/02.08440.1000.1220.014125150170
    8901062/02.210640.0790.0970.013145175195
    8906313/02.413420.0630.0780.012165200225
    8901074/02.616920.0500.0620.011195230260
    8906322502.920000.0420.0530.012215255290
    1135633003.224000.0350.0450.011240285320
    8901083503.428000.0300.0390.011260310350
    1135894003.532000.0260.0350.011280335380
    8901095003.840000.0210.0290.010320380430
    TBA6005.448000.0170.0250.010350420475
    8906337505.960000.0140.0220.010400475535
    11364710006.680000.0110.0180.009455545615
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).

    Stock Code Colors

    SizeBlackBrownOrangeYellowGreyWhiteRedBlueGreen
    BlackBrownOrangeYellowGrayWhiteRedBlueGreen
    14890700
    12113431678573
    10113449563196890146953539
    8113456643957952689588683655993
    6113464640110952671959726640128
    4113472588746476565476549643577952663
    2113498476523476531643544958009
    1113506
    1/0113514643973
    2/0113522591255
    3/0113530
    4/0113548587561
    250113555
    300113563
    350113571
    400113589
    500113597580165580166580168580169
    600113605
    750113613
    1000113647