SPEC 45003
1/C CU 600V XLPE RHH/RHW-2 USE-2 Silicone-Free Power Cable
Power Cable 600Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2 CT Rated

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2 Silicone-Free
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE E32071 {UL} XXX AWG (XX.X{mm2}) CU TYPE USE-2 OR RHH OR RHW-2 XX MILS XLP FOR CT USE SUN. RES. VW-1 600 VOLTS {NOM}-ANCE RHH/RHW-2 600V 90C
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
890700◊ | 14 | 7 | 0.071 | 45 | 0.161 | 12 | 20 |
113431◊ | 12 | 7 | 0.089 | 45 | 0.179 | 20 | 28 |
113449◊ | 10 | 7 | 0.113 | 45 | 0.203 | 32 | 42 |
113456◊ | 8 | 7 | 0.142 | 60 | 0.259 | 95 | 67 |
618689◊ | 6 | 7 | 0.178 | 60 | 0.304 | 81 | 109 |
113472◊ | 4 | 7 | 0.225 | 60 | 0.345 | 128 | 153 |
955872◊ | 2 | 7 | 0.283 | 60 | 0.403 | 205 | 244 |
113506◊ | 1 | 19 | 0.322 | 80 | 0.481 | 258 | 304 |
890105◊ | 1/0 | 19 | 0.362 | 80 | 0.522 | 325 | 390 |
890106◊ | 2/0 | 19 | 0.405 | 80 | 0.564 | 410 | 481 |
890631◊ | 3/0 | 19 | 0.456 | 80 | 0.616 | 518 | 598 |
890107◊ | 4/0 | 19 | 0.512 | 80 | 0.672 | 653 | 742 |
890632◊ | 250 | 37 | 0.558 | 95 | 0.748 | 771 | 884 |
113563◊ | 300 | 37 | 0.611 | 95 | 0.801 | 926 | 1023 |
890108◊ | 350 | 37 | 0.661 | 95 | 0.851 | 1081 | 1213 |
113589◊ | 400 | 37 | 0.706 | 95 | 0.896 | 1235 | 1345 |
890109◊ | 500 | 37 | 0.789 | 95 | 0.956 | 1544 | 1696 |
TBA◊ | 600 | 61 | 0.866 | 110 | 1.085 | 1853 | 2028 |
890633◊ | 750 | 61 | 0.968 | 110 | 1.188 | 2316 | 2534 |
113647◊ | 1000 | 61 | 1.117 | 110 | 1.337 | 3088 | 3283 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
890700◊ | 14 | 0.6 | 32 | 2.580 | 3.170 | 0.024 | 15 | 20 | 25 |
113431◊ | 12 | 0.7 | 52 | 1.630 | 2.000 | 0.021 | 20 | 25 | 30 |
113449◊ | 10 | 0.8 | 83 | 1.020 | 1.250 | 0.019 | 30 | 35 | 40 |
113456◊ | 8 | 1.0 | 132 | 0.640 | 0.786 | 0.019 | 40 | 50 | 55 |
618689◊ | 6 | 1.2 | 209 | 0.403 | 0.495 | 0.018 | 55 | 65 | 75 |
113472◊ | 4 | 1.3 | 333 | 0.253 | 0.310 | 0.015 | 70 | 85 | 95 |
955872◊ | 2 | 1.6 | 530 | 0.159 | 0.195 | 0.013 | 95 | 115 | 130 |
113506◊ | 1 | 1.9 | 669 | 0.126 | 0.154 | 0.014 | 110 | 130 | 145 |
890105◊ | 1/0 | 2.0 | 844 | 0.100 | 0.122 | 0.014 | 125 | 150 | 170 |
890106◊ | 2/0 | 2.2 | 1064 | 0.079 | 0.097 | 0.013 | 145 | 175 | 195 |
890631◊ | 3/0 | 2.4 | 1342 | 0.063 | 0.078 | 0.012 | 165 | 200 | 225 |
890107◊ | 4/0 | 2.6 | 1692 | 0.050 | 0.062 | 0.011 | 195 | 230 | 260 |
890632◊ | 250 | 2.9 | 2000 | 0.042 | 0.053 | 0.012 | 215 | 255 | 290 |
113563◊ | 300 | 3.2 | 2400 | 0.035 | 0.045 | 0.011 | 240 | 285 | 320 |
890108◊ | 350 | 3.4 | 2800 | 0.030 | 0.039 | 0.011 | 260 | 310 | 350 |
113589◊ | 400 | 3.5 | 3200 | 0.026 | 0.035 | 0.011 | 280 | 335 | 380 |
890109◊ | 500 | 3.8 | 4000 | 0.021 | 0.029 | 0.010 | 320 | 380 | 430 |
TBA◊ | 600 | 5.4 | 4800 | 0.017 | 0.025 | 0.010 | 350 | 420 | 475 |
890633◊ | 750 | 5.9 | 6000 | 0.014 | 0.022 | 0.010 | 400 | 475 | 535 |
113647◊ | 1000 | 6.6 | 8000 | 0.011 | 0.018 | 0.009 | 455 | 545 | 615 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Stock Code Colors
Size | Black | Brown | Orange | Yellow | Grey | White | Red | Blue | Green |
---|---|---|---|---|---|---|---|---|---|
![]() | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() | |
14 | 890700 | ||||||||
12 | 113431 | 678573 | |||||||
10 | 113449 | 563196 | 890146 | 953539 | |||||
8 | 113456 | 643957 | 952689 | 588683 | 655993 | ||||
6 | 113464 | 640110 | 952671 | 959726 | 640128 | ||||
4 | 113472 | 588746 | 476565 | 476549 | 643577 | 952663 | |||
2 | 113498 | 476523 | 476531 | 643544 | 958009 | ||||
1 | 113506 | ||||||||
1/0 | 113514 | 643973 | |||||||
2/0 | 113522 | 591255 | |||||||
3/0 | 113530 | ||||||||
4/0 | 113548 | 587561 | |||||||
250 | 113555 | ||||||||
300 | 113563 | ||||||||
350 | 113571 | ||||||||
400 | 113589 | ||||||||
500 | 113597 | 580165 | 580166 | 580168 | 580169 | ||||
600 | 113605 | ||||||||
750 | 113613 | ||||||||
1000 | 113647 |
Revision: 3.0.00C