SPEC 45005
Lead Free & Silicone-Free 1/C CU 600V EPR RHH/RHW-2 USE-2 CPE-TS Power Cable Royal Guard ®
Power Cable 600Volt Single Conductor Copper, Lead Free Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Cross-Linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

Construction:
- Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Binder Tape:Mylar Tape
- Insulation:Lead Free Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
- Overall Jacket:Lead Free & Silicone-Free Cross-Linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Sunlight and oil resistant.
Specifications:
Sample Print Legend:
SOUTHWIRE{R} ROYAL GUARD{R} XX AWG ({mm2}) E32071 MASTER-DESIGN {UL} RHH/RHW-2 OR USE-2 90{D}C 600V SUN RES VW-1 PRI PRII -40{D}C FT4 -- IEEE 1202 {MM/DD/YY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | |
592004 | 8 | 7 | 0.139 | 45 | 0.229 | 15 | 0.259 | 51 | 73 |
589493 | 6 | 7 | 0.174 | 45 | 0.264 | 30 | 0.324 | 81 | 116 |
589492 | 4 | 7 | 0.221 | 45 | 0.311 | 30 | 0.371 | 129 | 171 |
652233^ | 4 | 7 | 0.221 | 45 | 0.311 | 30 | 0.371 | 129 | 171 |
589491 | 2 | 7 | 0.277 | 45 | 0.367 | 30 | 0.427 | 205 | 257 |
594504^ | 2 | 7 | 0.277 | 45 | 0.367 | 30 | 0.427 | 205 | 257 |
589490 | 1 | 19 | 0.321 | 55 | 0.431 | 30 | 0.491 | 258 | 322 |
589495◊ | 1/0 | 19 | 0.360 | 55 | 0.470 | 45 | 0.560 | 326 | 412 |
589496◊ | 2/0 | 19 | 0.404 | 55 | 0.514 | 45 | 0.604 | 411 | 506 |
594506◊^ | 2/0 | 19 | 0.404 | 55 | 0.514 | 45 | 0.604 | 411 | 506 |
592011◊ | 3/0 | 19 | 0.454 | 55 | 0.564 | 45 | 0.654 | 518 | 623 |
589500◊ | 4/0 | 19 | 0.510 | 55 | 0.620 | 45 | 0.710 | 653 | 769 |
594507^ | 4/0 | 19 | 0.510 | 60 | 0.620 | 50 | 0.795 | 653 | 789 |
589497◊ | 250 | 37 | 0.558 | 65 | 0.688 | 65 | 0.872 | 772 | 984 |
589502 | 300 | 37 | 0.611 | 65 | 0.747 | 65 | 0.877 | 926 | 1095 |
589499◊ | 350 | 37 | 0.661 | 65 | 0.791 | 65 | 0.921 | 1081 | 1273 |
589501◊ | 500 | 37 | 0.789 | 65 | 0.919 | 65 | 1.049 | 1544 | 1767 |
595421 | 600 | 61 | 0.893 | 90 | 1.05 | 75 | 1.20 | 1853 | 2152 |
592017◊ | 750 | 61 | 0.968 | 80 | 1.128 | 65 | 1.258 | 2316 | 2608 |
589488 | 1000 | 91 | 1.117 | 80 | 1.277 | 65 | 1.407 | 3088 | 3418 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
^ Green Color
^ Green Color
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
592004 | 8 | 1.0 | 132 | 0.652 | 0.815 | 0.036 | 40 | 50 | 55 |
589493 | 6 | 1.3 | 210 | 0.411 | 0.514 | 0.036 | 55 | 65 | 75 |
589492 | 4 | 1.5 | 334 | 0.258 | 0.323 | 0.034 | 70 | 85 | 95 |
652233^ | 4 | 1.5 | 334 | 0.258 | 0.323 | 0.034 | 70 | 85 | 95 |
589491 | 2 | 1.7 | 531 | 0.162 | 0.203 | 0.032 | 95 | 115 | 130 |
594504^ | 2 | 1.7 | 531 | 0.162 | 0.203 | 0.032 | 95 | 115 | 130 |
589490 | 1 | 2.0 | 670 | 0.129 | 0.161 | 0.031 | 110 | 130 | 145 |
589495◊ | 1/0 | 2.2 | 845 | 0.102 | 0.128 | 0.032 | 125 | 150 | 170 |
589496◊ | 2/0 | 2.4 | 1065 | 0.081 | 0.102 | 0.031 | 145 | 175 | 195 |
594506◊^ | 2/0 | 2.4 | 1065 | 0.081 | 0.102 | 0.031 | 145 | 175 | 195 |
592011◊ | 3/0 | 2.6 | 1342 | 0.064 | 0.081 | 0.030 | 165 | 200 | 225 |
589500◊ | 4/0 | 2.8 | 1693 | 0.051 | 0.064 | 0.029 | 195 | 230 | 260 |
594507^ | 4/0 | 2.8 | 1693 | 0.051 | 0.064 | 0.029 | 195 | 230 | 260 |
589497◊ | 250 | 3.1 | 2000 | 0.043 | 0.055 | 0.029 | 215 | 255 | 290 |
589502 | 300 | 3.5 | 2400 | 0.036 | 0.046 | 0.03 | 240 | 285 | 320 |
589499◊ | 350 | 3.7 | 2800 | 0.031 | 0.039 | 0.029 | 260 | 310 | 350 |
589501◊ | 500 | 5.2 | 4000 | 0.022 | 0.028 | 0.028 | 320 | 380 | 430 |
595421 | 600 | 6 | 4800 | 0.018 | 0.024 | 0.026 | 350 | 420 | 475 |
592017◊ | 750 | 6.3 | 6000 | 0.014 | 0.020 | 0.028 | 400 | 475 | 535 |
589488 | 1000 | 7.0 | 8000 | 0.011 | 0.016 | 0.027 | 455 | 545 | 615 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
^ Green Color
^ Green Color
Size and Color
Size | GRN |
---|---|
4 | 652233 |
2 | 594504 |
2/0 | 594506 |
4/0 | 594507 |
Revision: 3.0.00C