SPEC 45008
1/C AL 600V XLPE RHH/RHW-2 USE-2 Power Cable
Power Cable 600Volt Single Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.
Specifications:
Sample Print Legend:
SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] AL RHH/RHW-2 USE-2 XLPE 600V For CT USE SUN. RES. For DIRECT BURIAL FT4 VW-1YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Insul. Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|
AWG/Kcmil | inch | mil | inch | lb/1000ft | lb/1000ft | |
272799 | 6 | 0.336 | 80 | 0.504 | 99 | 165 |
272807 | 4 | 0.336 | 80 | 0.504 | 99 | 165 |
272823 | 2 | 0.336 | 80 | 0.504 | 99 | 165 |
272831 | 1 | 0.336 | 80 | 0.504 | 99 | 165 |
576142 | 1/0 | 0.336 | 80 | 0.504 | 99 | 165 |
272856 | 2/0 | 0.376 | 80 | 0.536 | 125 | 186 |
272864 | 3/0 | 0.423 | 80 | 0.583 | 158 | 225 |
575991 | 4/0 | 0.475 | 80 | 0.635 | 199 | 279 |
576787 | 250 | 0.520 | 95 | 0.710 | 235 | 339 |
575992 | 300 | 0.570 | 95 | 0.760 | 282 | 392 |
272914 | 400 | 0.570 | 95 | 0.760 | 282 | 392 |
596530 | 700 | 0.570 | 95 | 0.760 | 282 | 392 |
TBA | 900 | 0.570 | 95 | 0.760 | 282 | 392 |
576137 | 350 | 0.616 | 95 | 0.809 | 329 | 452 |
567324 | 500 | 0.736 | 95 | 0.926 | 471 | 622 |
576141 | 600 | 0.805 | 110 | 1.033 | 565 | 734 |
576219 | 750 | 0.908 | 110 | 1.128 | 706 | 892 |
TBA | 1000 | 1.060 | 110 | 1.280 | 941 | 1155 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
272799 | 6 | 2.0 | 634 | 0.168 | 0.211 | 0.031 | 100 | 120 | 135 |
272807 | 4 | 2.0 | 634 | 0.168 | 0.211 | 0.031 | 100 | 120 | 135 |
272823 | 2 | 2.0 | 634 | 0.168 | 0.211 | 0.031 | 100 | 120 | 135 |
272831 | 1 | 2.0 | 634 | 0.168 | 0.211 | 0.031 | 100 | 120 | 135 |
576142 | 1/0 | 2.0 | 634 | 0.168 | 0.211 | 0.031 | 100 | 120 | 135 |
272856 | 2/0 | 2.1 | 799 | 0.133 | 0.167 | 0.030 | 115 | 135 | 150 |
272864 | 3/0 | 2.3 | 1007 | 0.105 | 0.132 | 0.029 | 130 | 155 | 175 |
575991 | 4/0 | 2.5 | 1270 | 0.084 | 0.105 | 0.028 | 150 | 180 | 205 |
576787 | 250 | 2.8 | 1500 | 0.071 | 0.089 | 0.029 | 170 | 205 | 230 |
575992 | 300 | 3.0 | 1800 | 0.059 | 0.075 | 0.028 | 195 | 230 | 260 |
272914 | 400 | 3.0 | 1800 | 0.059 | 0.075 | 0.028 | 195 | 230 | 260 |
596530 | 700 | 3.0 | 1800 | 0.059 | 0.075 | 0.028 | 195 | 230 | 260 |
TBA | 900 | 3.0 | 1800 | 0.059 | 0.075 | 0.028 | 195 | 230 | 260 |
576137 | 350 | 3.2 | 2100 | 0.051 | 0.064 | 0.028 | 210 | 250 | 280 |
567324 | 500 | 3.7 | 3000 | 0.035 | 0.045 | 0.027 | 260 | 310 | 350 |
576141 | 600 | 5.2 | 3600 | 0.030 | 0.038 | 0.027 | 285 | 340 | 385 |
576219 | 750 | 5.6 | 4500 | 0.024 | 0.031 | 0.027 | 320 | 385 | 435 |
TBA | 1000 | 6.4 | 6000 | 0.018 | 0.024 | 0.026 | 375 | 445 | 500 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).