SPEC 45041

MachineFLEX™ Tray Control Cable Cu 600/1000V PVC THHN TPE Jacket

Type TC-ER Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Sunlight Resistant Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s MachineFLEX™ control tray cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s machine tray cable is ideal for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind ener- gy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2277 Type WTTC
  • UL 13 Type PLTC-ER sizes 18-12AWG
  • UL 2250 Type ITC-ER on sizes 18-12 AWG
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Sample Print Legend:

    Print Legend 1:
    Southwire XXAWG (XXmm2) XX/C PVC/Nylon Type TC-ER EXXXXX (UL) 600V 90°C Dry 75C Wet Sun Res Oil Res I/II DIR BUR - 40°C OR MTW Flexing OR DP-1 OR WTTC 1000V OR AWM 2587 -- LLXXXXXX CSA AWM I/II A/B 105°C 1000V -40°C FT4 -- CSA FT4 CE RoHS -2 Made in USA

    Print Legend 2:
    SOUTHWIRE{R} XX AWG (XXmm2) 9/C PVC/NYLON TYPE TC-ER EXXXXX (UL) 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC-ER OR ITC-ER OR AWM 2587 -- LLXXXXX CSA CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 -- {NOM}-ANCE PLTC -- {CE} RoHS-2 MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsmilmilinchlb/1000ftinchAmpAmpAmp
    16 AWG
    6648041682620500.4311271.73101010
    18 AWG
    6770711821620450.266351.10777
    5815111831620450.281471.12777
    5826421841620450.306591.22777
    5826441851620450.332681.33777
    5815131871620450.358851.43777
    5826451891620450.4111071.64777
    58264618121620450.4561351.82777
    58264718181620450.5542072.22777
    64626218191620450.5632122.25777
    58151418251620600.6352452.54777
    16 AWG
    6770721622620500.294451.18101010
    5815151632620500.311601.24101010
    5826481642620500.339761.36101010
    5826491652620500.370891.48101010
    5815161672620500.4001131.60101010
    5826511692620500.4621441.85101010
    58265216122620500.5091992.04999
    58265316182620650.6232802.49999
    64626316192620650.6633102.65999
    58151716252620650.7173482.87888
    14 AWG
    6770731424120500.324591.29151515
    5815191434120500.342821.37151515
    5826541444120500.3751061.50151515
    5826551454120500.4111251.64151515
    5815211474120500.4451601.78141414
    6737951484120500.4801681.92141414
    5826561494120500.5162052.06141414
    58265714124120650.6002822.40101010
    58265814184120650.6974022.79101010
    58152214254120650.8065653.22999
    12 AWG
    6770741226520500.362801.45202020
    6771881236520500.3891081.56202020
    5826591246520500.4201471.68202020
    5826601256520500.4621761.85202020
    5826611276520500.5022272.01171717
    10 AWG
    67707510210525500.4301191.72282828
    67718910310525500.4621601.85282828
    58152310410525500.5022062.01282828
    58266210510525500.5302552.01282828
    58266310710525650.6083642.43242424
    6771908316836680.6262962.5405055
    6433678416836600.6803292.72324044
    6737978516836700.7484403.0324044
    6771916327336700.7254413.04556575
    6433696427336600.7604663.04406575
    6771924342746800.8986493.59686868
    6433714442746800.9697383.88686868
    67719323651461001.0709885.35929292
    6433732465146801.16211305.81929292
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Notes:

    Revision: 3.0.00M