SPEC 45055
Multi-Conductor TCU 600V EPR XHHW-2 CPE-TP Control Cable
Type TC-ER Control Cable 600 Volt Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. VW-1 Rated #14 - #10 AWG

Construction:
- Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) XHHW-2, 30 Mils thick for all cable sizes. VW-1 Rated #14 - #10 AWG
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated #14 - #10 AWG
Specifications:
Sample Print Legend:
SOUTHWIRE{R} 14 AWG (2.08mm2) 3/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 MASTER-DESIGN (UL) 600V 90{D}C DRY/90{D}C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- NOM-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90{D}C USA
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
16 AWG | |||||||||||||||||||
591931◊ | 16 | 2 | 0.056 | 30 | 45 | 0.323 | 16 | 55 | 4.180 | 5.226 | 1.3 | 10 | 10 | 10 | |||||
591932 | 16 | 3 | 0.056 | 30 | 45 | 0.341 | 24 | 68 | 4.180 | 5.226 | 1.4 | 10 | 10 | 10 | |||||
591933 | 16 | 4 | 0.056 | 30 | 45 | 0.371 | 32 | 84 | 4.180 | 5.226 | 1.5 | 10 | 10 | 10 | |||||
591934 | 16 | 5 | 0.056 | 30 | 45 | 0.404 | 40 | 100 | 4.180 | 5.226 | 1.6 | 10 | 10 | 10 | |||||
591935 | 16 | 7 | 0.056 | 30 | 45 | 0.439 | 56 | 128 | 4.180 | 5.226 | 1.8 | 9 | 10 | 10 | |||||
591936 | 16 | 9 | 0.056 | 30 | 45 | 0.510 | 72 | 164 | 4.180 | 5.226 | 2.0 | 9 | 10 | 10 | |||||
591937 | 16 | 12 | 0.056 | 30 | 60 | 0.604 | 97 | 228 | 4.180 | 5.226 | 2.4 | 6 | 7 | 9 | |||||
591938 | 16 | 15 | 0.056 | 30 | 60 | 0.668 | 121 | 278 | 4.180 | 5.226 | 2.7 | 6 | 7 | 9 | |||||
591939 | 16 | 19 | 0.056 | 30 | 60 | 0.702 | 153 | 329 | 4.180 | 5.226 | 2.8 | 6 | 7 | 9 | |||||
14 AWG | |||||||||||||||||||
591944◊ | 14 | 2 | 0.070 | 30 | 45 | 0.349 | 26 | 69 | 2.630 | 3.288 | 1.4 | 15 | 15 | 15 | |||||
591947◊ | 14 | 3 | 0.070 | 30 | 45 | 0.370 | 38 | 88 | 2.630 | 3.288 | 1.5 | 15 | 15 | 15 | |||||
591948◊ | 14 | 4 | 0.070 | 30 | 45 | 0.403 | 51 | 109 | 2.630 | 3.288 | 1.6 | 14 | 15 | 15 | |||||
591949◊ | 14 | 5 | 0.070 | 30 | 45 | 0.440 | 64 | 132 | 2.630 | 3.288 | 1.8 | 14 | 15 | 15 | |||||
591950◊ | 14 | 7 | 0.070 | 30 | 45 | 0.479 | 90 | 171 | 2.630 | 3.288 | 1.9 | 12 | 15 | 15 | |||||
591951◊ | 14 | 9 | 0.070 | 30 | 60 | 0.588 | 115 | 237 | 2.630 | 3.288 | 2.4 | 12 | 15 | 15 | |||||
591952◊ | 14 | 12 | 0.070 | 30 | 60 | 0.659 | 154 | 303 | 2.630 | 3.288 | 2.6 | 9 | 11 | 12 | |||||
591953◊ | 14 | 15 | 0.070 | 30 | 60 | 0.730 | 192 | 371 | 2.630 | 3.288 | 2.9 | 9 | 11 | 12 | |||||
591954◊ | 14 | 19 | 0.070 | 30 | 60 | 0.768 | 243 | 444 | 2.630 | 3.288 | 3.1 | 9 | 11 | 12 | |||||
591955 | 14 | 25 | 0.070 | 30 | 80 | 0.937 | 320 | 619 | 2.630 | 3.288 | 3.7 | 8 | 9 | 11 | |||||
591956 | 14 | 30 | 0.070 | 30 | 80 | 0.991 | 384 | 718 | 2.630 | 3.288 | 4.0 | 8 | 9 | 11 | |||||
591957 | 14 | 37 | 0.070 | 30 | 80 | 1.067 | 474 | 859 | 2.630 | 3.288 | 5.3 | 7 | 8 | 10 | |||||
12 AWG | |||||||||||||||||||
591959 | 12 | 2 | 0.087 | 30 | 45 | 0.384 | 41 | 91 | 1.660 | 2.075 | 1.5 | 20 | 20 | 20 | |||||
591960◊ | 12 | 3 | 0.087 | 30 | 45 | 0.408 | 61 | 118 | 1.660 | 2.075 | 1.6 | 20 | 20 | 20 | |||||
591962◊ | 12 | 4 | 0.087 | 30 | 45 | 0.445 | 81 | 149 | 1.660 | 2.075 | 1.8 | 16 | 20 | 20 | |||||
591963 | 12 | 5 | 0.087 | 30 | 45 | 0.487 | 102 | 181 | 1.660 | 2.075 | 1.9 | 16 | 20 | 20 | |||||
591964◊ | 12 | 7 | 0.087 | 30 | 45 | 0.532 | 143 | 237 | 1.660 | 2.075 | 2.1 | 14 | 17 | 20 | |||||
591965◊ | 12 | 9 | 0.087 | 30 | 60 | 0.651 | 183 | 325 | 1.660 | 2.075 | 2.6 | 14 | 17 | 20 | |||||
591966◊ | 12 | 12 | 0.087 | 30 | 60 | 0.732 | 244 | 419 | 1.660 | 2.075 | 2.9 | 10 | 12 | 15 | |||||
591967 | 12 | 15 | 0.087 | 30 | 60 | 0.813 | 305 | 516 | 1.660 | 2.075 | 3.3 | 10 | 12 | 15 | |||||
591968 | 12 | 19 | 0.087 | 30 | 80 | 0.896 | 387 | 657 | 1.660 | 2.075 | 3.6 | 10 | 12 | 15 | |||||
591969 | 12 | 25 | 0.087 | 30 | 80 | 1.043 | 509 | 859 | 1.660 | 2.075 | 5.2 | 9 | 11 | 13 | |||||
591970 | 12 | 30 | 0.087 | 30 | 80 | 1.104 | 611 | 1002 | 1.660 | 2.075 | 5.5 | 9 | 11 | 13 | |||||
591971 | 12 | 37 | 0.087 | 30 | 80 | 1.191 | 753 | 1205 | 1.660 | 2.075 | 6.0 | 8 | 10 | 12 | |||||
10 AWG | |||||||||||||||||||
591973◊ | 10 | 2 | 0.111 | 30 | 45 | 0.431 | 65 | 125 | 1.040 | 1.300 | 1.7 | 30 | 30 | 30 | |||||
591974◊ | 10 | 3 | 0.111 | 30 | 45 | 0.459 | 97 | 166 | 1.040 | 1.300 | 1.8 | 30 | 30 | 30 | |||||
591976◊ | 10 | 4 | 0.111 | 30 | 45 | 0.502 | 130 | 210 | 1.040 | 1.300 | 2.0 | 24 | 28 | 30 | |||||
591977◊ | 10 | 5 | 0.111 | 30 | 60 | 0.581 | 162 | 274 | 1.040 | 1.300 | 2.3 | 24 | 28 | 30 | |||||
591978 | 10 | 7 | 0.111 | 30 | 60 | 0.632 | 227 | 359 | 1.040 | 1.300 | 2.5 | 21 | 24 | 28 | |||||
591979 | 10 | 9 | 0.111 | 30 | 60 | 0.736 | 291 | 462 | 1.040 | 1.300 | 2.9 | 21 | 24 | 28 | |||||
591980 | 10 | 12 | 0.111 | 30 | 60 | 0.830 | 389 | 600 | 1.040 | 1.300 | 3.3 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C