SPEC 45252

3/C CU 600 or 1000 V XLPE XHHW-2 PVC Jacket Power Cable With Ground. Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. (When present, cable conductor sizes 8 & 6 AWG have an insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    Bare Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C

    Green Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    480590870.139450.2291 x 10600.615187307
    555196870.139450.229None x600.615155279
    480608670.174450.2641 x 8600.691297444
    555195670.174450.264None x600.691245382
    480616470.221450.3111 x 8600.791442607
    480624270.277450.3671 x 6800.953703941
    4806321190.321550.4311 x 6801.0918651159
    4806401/0190.360550.4701 x 6801.17510691397
    4806572/0190.404550.5141 x 6801.27013271693
    4806653/0190.454550.5641 x 4801.37817002112
    4806734/0190.510550.6201 x 4801.49921102575
    480681250370.558650.6881 x 4801.64624693012
    480699300370.611650.7411 x 31101.82129713667
    588013350370.641650.7771 x 3/01102.08137984571
    672206350370.661650.7911 x 11101.8635354300
    480707350370.661650.7911 x 31101.8634404196
    480715400370.706650.8361 x 31102.02639064727
    480723500370.789650.8961 x 21102.15548856064
    890148500370.789650.8961 x 1/01102.15549675897
    583697500370.789650.8961 x 2/01102.26249676065
    593173600610.866801.0261 x 3/01102.43661317303
    TBA600610.866801.0261 x 1/01102.43661317110
    890388600610.866801.0261 x 21102.43658226911
    672210600610.866801.0341 x 2501102.56763937544
    554410750610.968801.1281 x 11102.65672788510
    5807711000611.117801.2771 x 1/01403.038968411369
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    48059082.53960.6520.8150.033405055
    55519682.53960.6520.8150.033405055
    48060862.86300.4110.5140.031556575
    55519562.86300.4110.5140.031556575
    48061643.210020.2580.3230.030708595
    48062423.815930.1620.2030.02895115130
    48063215.520090.1290.1620.028110130145
    4806401/05.925340.1020.1280.028125150170
    4806572/06.431940.0810.1020.027145175195
    4806653/06.940270.0640.0810.027165200225
    4806734/07.550780.0510.0640.026195230260
    4806812508.260000.0430.0550.027215255290
    4806993009.172000.0360.0460.026240285320
    58801335012.584000.0310.0400.026260310350
    6722063509.384000.0310.0400.026260310350
    4807073509.384000.0310.0400.026260310350
    48071540012.296000.0880.0350.025280335380
    48072350013.2120000.0220.0290.025320380430
    89014850013.5120000.0220.0290.025320380430
    58369750013.5120000.0220.0290.025320380430
    59317360014.6144000.0180.0240.026350420475
    TBA60014.6144000.0180.0240.026350420475
    89038860014.6144000.0180.0240.026350420475
    67221060014.6144000.0180.0240.026350420475
    55441075015.9180000.0140.0200.025400475535
    580771100018.3180000.01080.01320.024455545615
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00C