SPEC 45268
4/C AL 600V PVC THHN PVC Power Cable With Ground
Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} 3/0 AWG AL 4 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 4 AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
TBA | 8 | 7 | 0.134 | 35 | 0.194 | 1 x 8 | 60 | 0.612 | 78 | 194 |
TBA | 6 | 7 | 0.169 | 35 | 0.229 | 1 x 8 | 60 | 0.697 | 115 | 254 |
TBA | 4 | 7 | 0.213 | 46 | 0.293 | 1 x 6 | 60 | 0.856 | 184 | 385 |
TBA | 2 | 7 | 0.268 | 46 | 0.348 | 1 x 6 | 80 | 1.029 | 277 | 560 |
TBA | 1 | 19 | 0.299 | 57 | 0.399 | 1 x 4 | 80 | 1.157 | 358 | 714 |
TBA | 1/0 | 19 | 0.336 | 57 | 0.436 | 1 x 4 | 80 | 1.246 | 441 | 835 |
675633 | 2/0 | 19 | 0.376 | 57 | 0.476 | 1 x 4 | 80 | 1.343 | 545 | 981 |
675635 | 3/0 | 19 | 0.423 | 57 | 0.523 | 1 x 4 | 80 | 1.456 | 678 | 1165 |
TBA | 4/0 | 19 | 0.475 | 57 | 0.575 | 1 x 2 | 80 | 1.582 | 867 | 1412 |
TBA | 250 | 37 | 0.520 | 65 | 0.650 | 1 x 1 | 110 | 1.789 | 1029 | 1772 |
599228 | 300 | 37 | 0.570 | 68 | 0.706 | 1 x 4 | 110 | 1.924 | 1202 | 2035 |
TBA | 350 | 37 | 0.616 | 65 | 0.746 | 1 x 2 | 110 | 2.021 | 1408 | 2285 |
TBA | 500 | 37 | 0.736 | 68 | 0.856 | 1 x 1 | 110 | 2.325 | 1982 | 3059 |
597539 | 500 | 37 | 0.736 | 68 | 0.856 | 1 x 2/0 | 110 | 2.325 | 2104 | 3199 |
TBA | 750 | 61 | 0.908 | 79 | 1.048 | 1 x 1/0 | 110 | 2.793 | 2953 | 4408 |
597540 | 750 | 61 | 0.908 | 79 | 1.048 | 1 x 3/0 | 110 | 2.925 | 4711 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
TBA | 8 | 2.4 | 396 | 1.070 | 1.345 | 0.033 | 28 | 32 | 36 |
TBA | 6 | 2.8 | 630 | 0.675 | 0.848 | 0.032 | 32 | 40 | 44 |
TBA | 4 | 3.4 | 1002 | 0.424 | 0.533 | 0.032 | 44 | 52 | 60 |
TBA | 2 | 5.1 | 1593 | 0.266 | 0.334 | 0.031 | 60 | 72 | 80 |
TBA | 1 | 5.8 | 2009 | 0.211 | 0.265 | 0.032 | 68 | 80 | 92 |
TBA | 1/0 | 6.2 | 2534 | 0.168 | 0.211 | 0.031 | 80 | 96 | 108 |
675633 | 2/0 | 6.7 | 3194 | 0.133 | 0.167 | 0.030 | 92 | 108 | 120 |
675635 | 3/0 | 7.3 | 4027 | 0.105 | 0.132 | 0.030 | 104 | 124 | 140 |
TBA | 4/0 | 7.9 | 5078 | 0.084 | 0.105 | 0.029 | 120 | 144 | 164 |
TBA | 250 | 8.9 | 6000 | 0.071 | 0.089 | 0.030 | 136 | 164 | 184 |
599228 | 300 | 9.6 | 7200 | 0.059 | 0.074 | 0.029 | 156 | 184 | 208 |
TBA | 350 | 12.1 | 8400 | 0.051 | 0.064 | 0.029 | 168 | 200 | 224 |
TBA | 500 | 14.0 | 12000 | 0.035 | 0.045 | 0.028 | 208 | 248 | 280 |
597539 | 500 | 14 | 12000 | 0.035 | 0.045 | 0.028 | 208 | 248 | 280 |
TBA | 750 | 16.8 | 18000 | 0.024 | 0.030 | 0.028 | 256 | 308 | 348 |
597540 | 750 | 17.6 | 18000 | 0.024 | 0.030 | 0.028 | 256 | 308 | 348 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C