SPEC 45314
4/C AL 600V XLPE XHHW-2 AIA PVC Power Cable With 50% Ground. Silicone Free
Type MC Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 3 Bare AL Ground. Silicone Free.

Construction:
- Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Three separate ground wires with a combined circular mil of 50% of the phase condutor. Class 4. B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler or Polypropylene filler
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE MASTER-DESIGN {UL} 4/C 750 KCMIL COMPACT 8000 AL. --- TRIPLE E ALLOY AA8176 XHHW CDRS 600 VOLTS GW 3 X 2/0 AWG 3E AL TYPE MC EZ-JKT FOR CT USE SUN. RES. DIRECT BURIAL 90{D}C
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | |
TBA | 1/0 | 19 | 0.336 | 55 | 0.446 | 3 x 6 | 1.287 | 50 | 1.387 | 635 | 976 |
TBA | 2/0 | 19 | 0.376 | 55 | 0.486 | 3 x 6 | 1.383 | 50 | 1.483 | 751 | 1128 |
TBA | 3/0 | 19 | 0.423 | 55 | 0.533 | 3 x 4 | 1.497 | 50 | 1.597 | 944 | 1365 |
TBA | 4/0 | 19 | 0.475 | 55 | 0.585 | 3 x 4 | 1.622 | 60 | 1.742 | 1126 | 1629 |
TBA | 250 | 37 | 0.520 | 65 | 0.650 | 3 x 2 | 1.879 | 60 | 1.999 | 1439 | 2060 |
TBA | 300 | 37 | 0.570 | 65 | 0.700 | 3 x 2 | 2.000 | 60 | 2.120 | 1649 | 2328 |
TBA | 350 | 37 | 0.616 | 65 | 0.746 | 3 x 2 | 2.111 | 60 | 2.231 | 1857 | 2591 |
TBA | 500 | 37 | 0.736 | 65 | 0.866 | 3 x 1 | 2.401 | 75 | 2.551 | 2528 | 3481 |
TBA | 600 | 61 | 0.813 | 80 | 0.973 | 3 x 1/0 | 2.659 | 75 | 2.809 | 3013 | 4202 |
587658◊ | 750 | 61 | 0.908 | 80 | 1.068 | 3 x 2/0 | 2.888 | 75 | 3.038 | 3698 | 5035 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
TBA | 1/0 | 9.7 | 2534 | 0.168 | 0.211 | 0.031 | 80 | 96 | 108 |
TBA | 2/0 | 10.4 | 3194 | 0.133 | 0.167 | 0.031 | 92 | 108 | 120 |
TBA | 3/0 | 11.2 | 4027 | 0.105 | 0.132 | 0.030 | 104 | 124 | 140 |
TBA | 4/0 | 12.2 | 5078 | 0.084 | 0.105 | 0.030 | 120 | 144 | 164 |
TBA | 250 | 14.0 | 6000 | 0.071 | 0.089 | 0.030 | 136 | 164 | 184 |
TBA | 300 | 14.8 | 7200 | 0.059 | 0.074 | 0.030 | 156 | 184 | 208 |
TBA | 350 | 15.6 | 8400 | 0.051 | 0.064 | 0.029 | 168 | 200 | 224 |
TBA | 500 | 17.9 | 12000 | 0.035 | 0.045 | 0.029 | 208 | 248 | 280 |
TBA | 600 | 19.7 | 14400 | 0.030 | 0.037 | 0.029 | 228 | 272 | 308 |
587658◊ | 750 | 21.3 | 18000 | 0.024 | 0.030 | 0.029 | 256 | 308 | 348 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C