SPEC 45502

1/C CU 2000V XLPE RHH/RHW-2 Power Cable

Power Cable 2000Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 MASTER-DESIGN {UL} XXX KCMIL (XXX{mm2}) CU TYPE RHH OR RHW-2 120 MILS XLP FOR CT USE SUN. RES. VW-1 2000 VOLTS {NOM}-ANCE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    TBA870.139700.2795177
    TBA670.174700.31481111
    TBA470.221700.361129166
    TBA270.277700.417205250
    TBA1190.321900.501258322
    TBA1/0190.360900.540326396
    TBA2/0190.404900.584411489
    TBA3/0190.454900.634518604
    TBA4/0190.510900.690653749
    TBA250370.5581050.768772891
    TBA350370.6611050.87110811219
    568018500370.7891050.99915441706
    TBA600610.8661201.10618532051
    648750750610.9681201.20823162534
    TBA1000611.1171201.35730883336
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA82.21320.6520.8150.038405055
    TBA62.52100.4110.5140.035556575
    TBA42.93340.2580.3230.033708595
    TBA23.35310.1620.2030.03195115130
    TBA14.06700.1290.1610.032110130145
    TBA1/04.38450.1020.1280.031125150170
    TBA2/04.710650.0810.1020.030145175195
    TBA3/05.113420.0640.0810.029165200225
    TBA4/05.516930.0510.0640.029195230260
    TBA2506.120000.0430.0550.029215255290
    TBA3507.028000.0310.0400.028260310350
    5680185008.040000.0220.0280.027320380430
    TBA6008.848000.0180.0240.027350420475
    6487507509.760000.0140.0200.027400475535
    TBA100010.980000.0110.0160.026455545615
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).

    Revision: 3.0.00C