SPEC 81111

15kV AL 133% TRXLPE Full Neutral LLDPE Primary UD

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Full Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper full concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS TRXLPE INSULATION 220 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    613418**2 (1)0.2580.7352200.81510x140.263501.0435058.3398
    6103062 (7)0.2830.7602200.84010x140.263501.0685298.5398
    TBA1 (1)0.2890.7662200.84613x140.202501.0745718.5502
    TBA1 (19)0.3220.7992200.87913x140.202501.1075998.8502
    6123591/0 (1)0.3250.8022200.88216x140.164501.1136528.9634
    6103071/0 (19)0.3520.8292200.90916x140.164501.1376669.0634
    606978**2/0 (19)0.3950.8722200.95220x140.128501.2127729.6799
    TBA2/0 (19)0.3950.8722200.95213x120.128501.2127949.6799
    TBA3/0 (19)0.4430.9202201.00016x120.104501.26090810.1007
    678102^4/0 (19)0.4980.9752201.05520x120.080501.320107010.1270
    6104064/0 (19)0.4980.9752201.05520x120.080501.320107010.1270
    TBA250 (37)0.5581.0442201.14416x100.065501.448129811.51500
    TBA350 (37)0.6611.1472201.24716x90.052501.576160512.62100
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    **HI-DRI-PLUS.
    ^ Non Moisture Block
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.2660.3340.0620.0510.1390.3620.568+j0.1250.336+j0.0513660.2120150
    2 (7)0.2660.3340.0590.0490.1470.3820.568+j0.1240.336+j0.0493660.2120150
    1 (1)0.2110.2650.0580.0490.1490.3870.456+j0.0910.267+j0.0494758.3140175
    1 (19)0.2110.2650.0540.0480.1590.4130.456+j0.0900.267+j0.0474758.3140175
    1/0 (1)0.1680.2110.0540.0470.1600.4160.371+j0.0710.213+j0.0475856.3155195
    1/0 (19)0.1680.2110.0510.0460.1680.4370.371+j0.0700.213+j0.0465856.3155195
    2/0 (19)0.1330.1670.0480.0450.1810.4710.296+j0.0570.170+j0.0457560.0180225
    2/0 (19)0.1330.1670.0480.0450.1810.4710.296+j0.0570.170+j0.0457560.0180225
    3/0 (19)0.1050.1320.0440.0440.1960.5080.238+j0.0470.136+j0.0439304.6205250
    4/0 (19)0.08360.1050.0410.0430.2120.5510.186+j0.0400.110+j0.04112017.3235285
    4/0 (19)0.08360.1050.0410.0430.2120.5510.186+j0.0400.110+j0.04112017.3235285
    250 (37)0.07070.0890.0370.0420.2330.6040.156+j0.0340.095+j0.03914790.5
    350 (37)0.05050.0640.0330.0400.2630.6830.117+j0.0310.070+j0.03718652.0305370
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    613418**2 (1)6.5518.675.5920.7010x140.861.2726.49752210.821771
    6103062 (7)7.1919.305.5921.3410x140.861.2727.13787215.901771
    TBA1 (1)7.3419.465.5921.4913x140.661.2727.28850215.902234
    TBA1 (19)8.1820.295.5922.3313x140.661.2728.12891223.522234
    6123591/0 (1)8.2520.375.5922.4016x140.541.2728.27970226.062821
    6103071/0 (19)8.9421.065.5923.0916x140.541.2728.88991228.602821
    606978**2/0 (19)10.0322.155.5924.1820x140.421.2730.781149243.843556
    TBA2/0 (19)10.0322.155.5924.1813x120.421.2730.781182243.843556
    TBA3/0 (19)11.2523.375.5925.4016x120.341.2732.001351254.004481
    678102^4/0 (19)12.6524.765.5926.8020x120.261.2733.531592254.005652
    6104064/0 (19)12.6524.765.5926.8020x120.261.2733.531592254.005652
    TBA250 (37)14.1726.525.5929.0616x100.211.2736.781932292.106675
    TBA350 (37)16.7929.135.5931.6716x90.171.2740.032389320.049345
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    **HI-DRI-PLUS.
    ^ Non Moisture Block
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.87271.100.01890.16730.4561.18770.568+j0.1250.336+j0.0513660.2120150
    2 (7)0.87271.100.01800.16080.4821.25330.568+j0.1240.336+j0.0493660.2120150
    1 (1)0.69230.870.01770.16080.4891.26970.456+j0.0910.267+j0.0494758.3140175
    1 (19)0.69230.870.01650.15750.5221.35500.456+j0.0900.267+j0.0474758.3140175
    1/0 (1)0.55120.690.01650.15420.5251.36480.371+j0.0710.213+j0.0475856.3155195
    1/0 (19)0.55120.690.01550.15090.5511.43370.371+j0.0700.213+j0.0465856.3155195
    2/0 (19)0.43640.550.01460.14760.5941.54530.296+j0.0570.170+j0.0457560.0180225
    2/0 (19)0.43640.550.01460.14760.5941.54530.296+j0.0570.170+j0.0457560.0180225
    3/0 (19)0.34450.430.01340.14440.6431.66670.238+j0.0470.136+j0.0439304.6205250
    4/0 (19)0.27430.340.01250.14110.6961.80770.186+j0.0400.110+j0.04112017.3235285
    4/0 (19)0.27430.340.01250.14110.6961.80770.186+j0.0400.110+j0.04112017.3235285
    250 (37)0.23200.290.01130.13780.7641.98160.156+j0.0340.095+j0.03914790.5
    350 (37)0.16570.210.01010.13120.8632.24080.117+j0.0310.070+j0.03718652.0305370
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C