SPEC 81242

35kV AL 100% TRXLPE One-Third Neutral LLDPE Primary UD

Single Conductor, 345 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:345 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 35kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 35000 VOLTS TRXLPE INSULATION 345 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA1/0 (1)0.3251.0523451.1526x140.438501.38075011.634
    615150^1/0 (19)0.3521.0793451.1796x140.438501.40777811.2634
    6207261/0 (19)0.3521.0793451.1796x140.438501.40777811.2634
    619330^†1/0 (19)0.3521.0793451.17911x140.438501.41083711.634
    6278792/0 (19)0.3951.1223451.2227x140.376501.450847110799
    TBA3/0 (19)0.4431.1703451.2709x140.292501.49893711.91007
    2548154/0 (19)0.4981.2253451.32511x140.239501.553104212.41270
    615151^4/0 (19)0.4981.2253451.32511x140.239501.553104212.41270
    626296!^4/0 (19)0.4981.2183451.32811x140.239501.556104212.41270
    618436§250 (37)0.5581.2943451.39413x140.202501.626116313.01500
    584524^^350 (37)0.6611.3973451.49718x140.146801.783145214.22100
    619322350 (37)0.6611.3973451.49718x140.146801.785146314.2100
    620816^^500 (37)0.7891.5253451.62516x120.104801.945183715.3000
    614633500 (37)0.7891.5253451.62516x120.104801.945183715.3000
    626322^500 (37)0.7891.5193451.62916x120.104771.945182615.3000
    625222500 (37)0.7891.5253451.62525x140.104801.945183715.3000
    257724750 (61)0.9681.7133451.84324x120.069802.163243317.34500
    6146341000 (61)1.1171.8623451.99220x100.052802.356301118.86000
    6173681250 (91)1.2502.0173452.14725x100.041802.536358920.27500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ! UL listed MV-90 Rated
    ^ HiDri Plus® - Water Blocking Powder
    ^^ HiDri Plus® - Water Blocking Powder. All Black Jacket
    † 2/3 Concentric Neutral
    § HiDri Plus® - Water Blocking Powder. CSA Listed
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (1)0.1680.2110.0730.0520.2781.6870.523+j0.2380.212+j0.0522251.8160195
    1/0 (19)0.1680.2110.0690.0510.2911.7650.522+j0.2370.212+j0.0512251.8160195
    1/0 (19)0.1680.2110.0690.0510.2781.6870.522+j0.2370.212+j0.0512251.8160195
    1/0 (19)0.1680.2110.0690.0510.2911.7650.522+j0.2370.212+j0.0512251.8160195
    2/0 (19)0.1330.1670.0650.0500.3111.8860.456+j0.1970.168+j0.0492627.1185220
    3/0 (19)0.1050.1320.0610.0480.3332.0200.381+j0.1440.133+j0.0483377.6210250
    4/0 (19)0.08360.1050.0560.0460.3582.1730.320+j0.1120.106+j0.0464128.2235285
    4/0 (19)0.08360.1050.0560.0460.3582.1730.320+j0.1120.106+j0.0464128.2235285
    4/0 (19)0.08360.1050.0560.0460.3582.1730.320+j0.1120.106+j0.0464128.2235285
    250 (37)0.07070.0890.0520.0440.3902.3630.278+j0.0900.091+j0.0444878.8
    350 (37)0.05050.0640.0460.0430.4362.6430.207+j0.0620.066+j0.0436755.3315370
    350 (37)0.05050.0640.0460.0430.4362.6430.207+j0.0620.066+j0.0436755.3315370
    500 (37)0.03540.0450.0410.0410.4932.9890.151+j0.0460.048+j0.0409540.3380450
    500 (37)0.03540.0450.0410.0410.4932.9890.151+j0.0460.048+j0.0409540.3380450
    500 (37)0.03540.0450.0410.0410.4932.9890.151+j0.0460.048+j0.0409540.3380450
    500 (37)0.03540.0450.0410.0410.4932.9890.151+j0.0460.048+j0.0409540.3380450
    750 (61)0.02360.0300.0350.0390.5763.4920.102+j0.0330.035+j0.03714310.5470545
    1000 (61)0.01770.0230.0320.0380.6413.8890.077+j0.0290.029+j0.03518956.4530620
    1250 (91)0.01410.0190.0280.0370.7094.3000.062+j0.0270.025+j0.03323905.5
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA1/0 (1)8.2526.728.7629.266x141.441.2735.051116279.402821
    615150^1/0 (19)8.9427.418.7629.956x141.441.2735.741158284.482821
    6207261/0 (19)8.9427.418.7629.956x141.441.2735.741158284.482821
    619330^†1/0 (19)8.9427.418.7629.9511x141.441.2735.811246279.402821
    6278792/0 (19)10.0328.508.7631.047x141.231.2736.8312602794.003556
    TBA3/0 (19)11.2529.728.7632.269x140.961.2738.051394302.264481
    2548154/0 (19)12.6531.128.7633.6511x140.781.2739.451551314.965652
    615151^4/0 (19)12.6531.128.7633.6511x140.781.2739.451551314.965652
    626296!^4/0 (19)12.6530.948.7633.7311x140.781.2739.521551314.965652
    618436§250 (37)14.1732.878.7635.4113x140.661.2741.301731330.206675
    584524^^350 (37)16.7935.488.7638.0218x140.482.0345.292161360.689345
    619322350 (37)16.7935.488.7638.0218x140.482.0345.342177355.609345
    620816^^500 (37)20.0438.738.7641.2816x120.342.0349.402734381.0013350
    614633500 (37)20.0438.738.7641.2816x120.342.0349.402734381.0013350
    626322^500 (37)20.0438.588.7641.3816x120.341.9649.402717381.0013350
    625222500 (37)20.0438.738.7641.2825x140.342.0349.402734381.0013350
    257724750 (61)24.5943.518.7646.8124x120.232.0354.943621439.4220025
    6146341000 (61)28.3747.298.7650.6020x100.172.0359.844481477.5226700
    6173681250 (91)31.7551.238.7654.5325x100.132.0364.415341513.0833375
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ! UL listed MV-90 Rated
    ^ HiDri Plus® - Water Blocking Powder
    ^^ HiDri Plus® - Water Blocking Powder. All Black Jacket
    † 2/3 Concentric Neutral
    § HiDri Plus® - Water Blocking Powder. CSA Listed
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (1)0.55120.690.02230.17060.9125.53480.523+j0.2380.212+j0.0522251.8160195
    1/0 (19)0.55120.690.02100.16730.9555.79070.522+j0.2370.212+j0.0512251.8160195
    1/0 (19)0.55120.690.02100.16730.9125.53480.522+j0.2370.212+j0.0512251.8160195
    1/0 (19)0.55120.690.02100.16730.9555.79070.522+j0.2370.212+j0.0512251.8160195
    2/0 (19)0.43640.550.01980.16401.0206.18770.456+j0.1970.168+j0.0492627.1185220
    3/0 (19)0.34450.430.01860.15751.0936.62730.381+j0.1440.133+j0.0483377.6210250
    4/0 (19)0.27430.340.01710.15091.1757.12930.320+j0.1120.106+j0.0464128.2235285
    4/0 (19)0.27430.340.01710.15091.1757.12930.320+j0.1120.106+j0.0464128.2235285
    4/0 (19)0.27430.340.01710.15091.1757.12930.320+j0.1120.106+j0.0464128.2235285
    250 (37)0.23200.290.01580.14441.2807.75260.278+j0.0900.091+j0.0444878.8
    350 (37)0.16570.210.01400.14111.4308.67130.207+j0.0620.066+j0.0436755.3315370
    350 (37)0.16570.210.01400.14111.4308.67130.207+j0.0620.066+j0.0436755.3315370
    500 (37)0.11610.150.01250.13451.6179.80640.151+j0.0460.048+j0.0409540.3380450
    500 (37)0.11610.150.01250.13451.6179.80640.151+j0.0460.048+j0.0409540.3380450
    500 (37)0.11610.150.01250.13451.6179.80640.151+j0.0460.048+j0.0409540.3380450
    500 (37)0.11610.150.01250.13451.6179.80640.151+j0.0460.048+j0.0409540.3380450
    750 (61)0.07740.100.01070.12801.89011.45670.102+j0.0330.035+j0.03714310.5470545
    1000 (61)0.05810.080.00980.12472.10312.75920.077+j0.0290.029+j0.03518956.4530620
    1250 (91)0.04630.060.00850.12142.32614.10760.062+j0.0270.025+j0.03323905.5
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C