SPEC 83227

Triplex XLPE Service Drop. AAC Neutral - Messenger

Aluminum Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:AAC Neutral

Applications and Features:

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/Kcmilinchlb/1000ft
    TBAHaiotis610.162450.25260.54497
    TBAPatella670.178450.26860.579103
    TBAFusus410.204450.29440.636145
    104729Oyster470.225450.31540.68154
    104737Clam270.283450.37320.806233
    623542Mussel270.283450.37340.806224
    TBAPurpura1/090.352600.4721/01.02368
    104745Murex1/070.357600.4771/01.03374
    TBATrophon2/0110.395600.5152/01.112456
    104760Nassa2/070.402600.5222/01.128462
    TBAMelita3/0170.443600.5633/01.216562
    104794Portunus4/0180.498600.6184/01.335696
    250407Nannynose336.4190.645600.805336.41.7391118
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Stock NumberCode WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    TBAHaiotis65630.65230.83630.03180.005385
    TBAPatella65630.66530.8530.03270.005485
    TBAFusus48810.410.52580.03010.0066115
    104729Oyster48810.41830.53630.0310.0068115
    104737Clam213500.26310.33730.02960.0086150
    623542Mussel213500.26310.33730.02960.0086150
    TBAPurpura1/019900.16530.2120.02990.0107205
    104745Murex1/019900.16530.2120.02990.0108205
    TBATrophon2/025100.13120.16820.0290.0121235
    104760Nassa2/025100.13120.16820.02930.0122235
    TBAMelita3/033100.1040.13350.0280.0139275
    104794Portunus4/040200.08250.10590.02730.0157315
    250407Nannynose336.461460.05190.06670.02740.0204420
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Sizes of AAAC neutrals are not the AAAC size, but are the size of an ACSR of equal diameter.
    7. Ampacity based on conductor temperature of 90°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Neutral Code Word

    Size-StrandsCode WordOD (inches)
    #6-7Peachbell0.184
    #4-7Rose0..232
    #2-7Iris0.292
    1/0-7Poppy0.368
    2/0-7Aster0.414
    3/0-19Primrose0.470
    4/0-19Sunflower0.528
    336.4-19Tulip0.665