SPEC 83033

Triplex 600 Volt Underground Service Entrance. Hi-Score Optional

Aluminum Conductor. Cross-linked Polyethylene (XLP) Insulation. HI-SCORE available upon request.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE). LLDPE or HDPE based polymer
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)

Applications and Features:

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two-phase conductors and one neutral conductor are cabled together to produce the triplex cable configuration. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-81-570 Standard for 600 Volt Rated Cables of Ruggedized Design for Direct Burial Installations as Single Conductors or Assemblies of Single Conductors
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandNeutral Insul. ThicknessDia. Over Neutral InsulationApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.milinchinchlb/1000ft
    TBABlank870.142600.26287600.2620.565193
    TBAErskine670.178600.29867600.2980.644134
    TBAVassar470.225600.34547600.3450.745191
    TBAStephens270.283600.40347600.3450.87249
    TBARamapo270.283600.40327600.4030.87278
    TBABrenau1/090.352800.51227600.4031.106387
    TBABergen1/090.352800.5121/09800.5121.106441
    TBAConverse2/0110.395800.55519800.4731.199478
    TBAHunter2/0110.395800.5552/011800.5551.199535
    TBAHollins3/0170.443800.6031/09800.5121.302581
    TBARockland3/0170.443800.6033/017800.6031.302651
    612667Sweetbriar4/0180.498800.6582/011800.5551.421709
    TBAMonmouth4/0180.498800.6584/018800.6581.421796
    310748Pratt250220.542800.7323/017800.6031.581853
    322073Gloucester350300.641950.8313/018800.6581.7951071
    TBAHolyoke500340.766950.95630037950.7841.9121830
    656744Rider500340.766950.95635030950.8312.1151605
    TBAFairfield750610.9391101.15950037800.9492.3162784
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Stock NumberCode WordPhase Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzGMRAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftftAmpAmp
    TBABlank81.05741.35580.03740.00435570
    TBAErskine60.66530.8530.03510.00547095
    TBAVassar40.41830.53630.03310.006890125
    TBAStephens20.26310.33730.03140.0086120165
    TBARamapo20.26310.33730.03140.0086120165
    TBABrenau1/00.16530.2120.03170.0107160215
    TBABergen1/00.16530.2120.03170.0107160215
    TBAConverse2/00.13120.16820.03080.0121180245
    TBAHunter2/00.13120.16820.03080.0121180245
    TBAHollins3/00.1040.13350.02950.0139205280
    TBARockland3/00.1040.13350.02950.0139205280
    612667Sweetbriar4/00.08250.10590.02880.0157240315
    TBAMonmouth4/00.08250.10590.02880.0157240315
    310748Pratt2500.06980.08970.02910.0172265345
    322073Gloucester3500.04990.06410.02810.0204320415
    TBAHolyoke5000.03490.0450.0270.0252395495
    656744Rider5000.03490.0450.0270.0252395495
    TBAFairfield7500.02310.03290.02470.0313495620
    Notes:
    1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
    2. Triple parallel inductive reactance calculation assumes the phase conductors are adjacent to one another.
    3. Conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the Phase conductors only.
    6. Ampacity based on 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor.