SPEC 85008
Multi-Conductor CU 600 V FR-XLPE Thermoset CPE-TS Jacket Control Cable Color Method 1 Table 1
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoset Chlorinated Polyethylene (CPE-TS) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoset Chlorinated Polyethylene (CPE-TS) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Specifications:
Sample Print Legend:
Non UL:
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT TYPE TC 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
UL:
SOUTHWIRE MASTER-DESIGN E75755 {UL} XX AWG 3/C TYPE TC-ER FR-XLPE XHHW-2 CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT TYPE TC 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
UL:
SOUTHWIRE MASTER-DESIGN E75755 {UL} XX AWG 3/C TYPE TC-ER FR-XLPE XHHW-2 CDRS 90{D}C CPE JKT SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
18 AWG | |||||||||||||||||||
622124 | 18 | 4 | .046 | 25 | 45 | 0.329 | 20 | 58 | 6.67 | 8.68 | 1.3 | - | - | 11 | |||||
16 AWG | |||||||||||||||||||
628795^ | 16 | 2 | .056 | 25 | 45 | 0.319 | 16 | 51 | 4.181 | 5.439 | 1.3 | - | - | 18 | |||||
14 AWG | |||||||||||||||||||
620339^ | 14 | 3 | 0.070 | 30 | 45 | 0.389 | 38 | 93 | 2.631 | 3.423 | 1.6 | 15 | 20 | 25 | |||||
620341^† | 14 | 4 | 0.070 | 30 | 45 | 0.421 | 51 | 110 | 2.631 | 3.423 | 1.7 | 12 | 16 | 20 | |||||
620361^ | 14 | 7 | 0.070 | 30 | 45 | 0.498 | 90 | 173 | 2.631 | 3.423 | 2.0 | 11 | 14 | 18 | |||||
12 AWG | |||||||||||||||||||
622177 | 12 | 2 | 0.087 | 30 | 45 | 0.384 | 41 | 90 | 1.660 | 2.075 | 1.5 | 20 | 20 | 20 | |||||
669327 | 12 | 3 | 0.087 | 30 | 45 | 0.416 | 61 | 117 | 1.660 | 2.075 | 1.6 | 20 | 20 | 20 | |||||
622179 | 12 | 4 | 0.087 | 30 | 45 | 0.445 | 81 | 148 | 1.660 | 2.075 | 1.8 | 16 | 20 | 20 | |||||
618423 | 12 | 4 | 0.087 | 30 | 45 | 0.445 | 81 | 143 | 1.660 | 2.075 | 1.8 | 16 | 20 | 20 | |||||
669323 | 12 | 7 | 0.087 | 30 | 60 | 0.572 | 143 | 250 | 1.660 | 2.075 | 2.3 | 14 | 17 | 20 | |||||
620733^^ | 12 | 7 | 0.087 | 30 | 60 | 0.589 | 143 | 298 | 1.660 | 2.075 | 2.4 | 14 | 17 | 20 | |||||
669319 | 12 | 12 | 0.087 | 30 | 60 | 0.742 | 244 | 406 | 1.660 | 2.075 | 3.0 | 10 | 12 | 15 | |||||
620280 | 12 | 16 | 0.087 | 30 | 80 | 0.861 | 326 | 552 | 1.660 | 2.075 | 3.4 | 10 | 12 | 15 | |||||
10 AWG | |||||||||||||||||||
622195 | 10 | 2 | 0.111 | 30 | 45 | 0.431 | 65 | 124 | 1.040 | 1.300 | 1.7 | 30 | 30 | 30 | |||||
620353^† | 10 | 3 | 0.111 | 30 | 45 | 0.480 | 97 | 1170 | 1.040 | 1.300 | 2.0 | 30 | 30 | 30 | |||||
622199 | 10 | 4 | 0.111 | 30 | 45 | 0.502 | 130 | 210 | 1.040 | 1.300 | 2.0 | 24 | 28 | 30 | |||||
607188^ | 10 | 4 | 0.111 | 30 | 60 | 0.561 | 130 | 225 | 1.040 | 1.300 | 2.0 | 24 | 28 | 30 | |||||
620359^ | 10 | 9 | 0.111 | 30 | 60 | 0.761 | 291 | 450 | 1.040 | 1.353 | 3.0 | 21 | 25 | 28 | |||||
626480^† | 10 | 12 | 0.111 | 30 | 80 | 0.896 | 389 | 615 | 1.040 | 1.353 | 3.6 | 15 | 18 | 20 | |||||
620388^ | 6 | 4 | 0.178 | 45 | 60 | 0.783 | 327 | 508 | 0.411 | 0.535 | 3.1 | 44 | 52 | 60 | |||||
620390^^ | 3 | 4 | 0.225 | 47 | 60 | 0.817 | 391 | 557 | 0.2580 | 0.336 | 3.3 | 70 | 85 | 95 | |||||
620392^ | 4 | 4 | 0.225 | 47 | 80 | 0.936 | 521 | 805 | 0.2580 | 0.336 | 3.7 | 56 | 68 | 76 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^Tinned copper
^^19 strand conductor
† UL Listed
^Tinned copper
^^19 strand conductor
† UL Listed
Revision: 3.0.00C