SPEC 85024

Multi-Conductor CU 600 V FR-XLPE Shielded Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mils tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} XX AWG CU X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT SHIELDED 600V SUN RES MM/YYYY {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.inchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    14 AWG
    TBA1420.07030450.34926682.6303.2884.2151515
    TBA1430.07030450.37038872.6303.2884.4151515
    TBA1440.07030450.403511092.6303.2884.8141515
    TBA1450.07030450.440641322.6303.2885.3141515
    TBA1460.07030450.479771552.6303.2885.8141515
    TBA1470.07030450.479901712.6303.2885.8121515
    TBA1480.07030450.5191021952.6303.2886.2121515
    TBA1490.07030600.5881152362.6303.2887.1121515
    TBA14100.07030600.6381282662.6303.2887.791112
    TBA14120.07030600.6591543032.6303.2887.991112
    620673!14120.07030600.6891953382.6303.2888.391112
    TBA14150.07030600.7301923712.6303.2888.891112
    TBA14190.07030600.7682434462.6303.2889.291112
    TBA14200.07030600.8082564752.6303.2889.791112
    TBA14250.07030800.9373206192.6303.28811.28911
    TBA14300.07030800.9913847192.6303.28811.98911
    TBA14370.07030801.0674748622.6303.28812.87810
    12 AWG
    TBA1220.08730450.38441901.6602.0754.6202020
    TBA1230.08730450.408611181.6602.0754.9202020
    TBA1240.08730450.445811481.6602.0755.3162020
    TBA1250.08730450.4871021811.6602.0755.8162020
    TBA1260.08730450.5321222141.6602.0756.4162020
    TBA1270.08730450.5321432371.6602.0756.4141720
    TBA1280.08730600.6071632881.6602.0757.3141720
    TBA12100.08730600.7092043651.6602.0758.5101215
    625170^^12120.08730600.7322444191.6602.0758.8101215
    TBA12150.08730600.8133055161.6602.0759.8101215
    TBA12190.08730800.8963876571.6602.07510.8101215
    TBA12200.08730800.9424076991.6602.07511.3101215
    TBA12250.08730801.0435098601.6602.07512.591113
    TBA12300.08730801.10461110051.6602.07513.391113
    TBA12370.08730801.19175312111.6602.07514.381012
    10 AWG
    606612^1020.11130450.431651241.0401.3005.2303030
    TBA1030.11130450.459971651.0401.3005.5303030
    6196691040.11130600.5571302561.0401.3006.7242830
    TBA1050.11130600.5811622731.0401.3007242830
    TBA1060.11130600.6321943231.0401.3007.6242830
    TBA1070.11130600.6322273581.0401.3007.6212428
    TBA1080.11130600.6852594101.0401.3008.2212428
    TBA1090.11130600.7362914611.0401.3008.8212428
    TBA10100.11130600.8033245191.0401.3009.6151720
    606609^10120.11130800.9004576891.0401.30010.8151720
    61987010120.11130800.9003896791.0401.30010.8151720
    TBA10150.11130800.9644867771.0401.30011.6151720
    TBA10190.11130801.0146159411.0401.30012.2151720
    TBA10200.11130801.06764810011.0401.30012.8151720
    TBA10250.11130801.18481012361.0401.30014.2131518
    TBA10300.11130801.25497114501.0401.30015.1131518
    TBA10370.11130801.355119817551.0401.30016.3121416
    6036098120.14345801.15770810690.6520.81513.9202527
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
    ^ UL Listed part number
    ^^ Tinned Copper
    ! 19 stranded per ASTM B787