SPEC 85047
Multi-Conductor CU 1000 V FR-XLPE Shielded Thermoset LSZH Jacket Control Cable Color Method 1 Table 1
Control Cable 1000 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shielding:5 mils tape shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket
Applications and Features:
Southwire’s 1000 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS SHIELDED 90C LSZH JACKET SUNLIGHT RESISTANT DIRECT BURIAL 1000V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C LSZH JACKET SUN RES FT-4 DIR BUR 1000V YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
14 AWG | |||||||||||||||||||
621892 | 14 | 12 | 0.070 | 45 | 60 | 0.820 | 206 | 419 | 2.631 | 3.423 | 9.8 | 8 | 10 | 13 | |||||
12 AWG | |||||||||||||||||||
626172! | 12 | 7 | 0.087 | 45 | 60 | 0.676 | 183 | 339 | 1.662 | 2.162 | 8.1 | 14 | 18 | 21 | |||||
10 AWG | |||||||||||||||||||
621899 | 10 | 4 | 0.111 | 30 | 60 | 0.561 | 163 | 267 | 1.041 | 1.353 | 6.7 | 24 | 28 | 32 | |||||
621885 | 10 | 3 | 0.111 | 45 | 60 | 0.582 | 132 | 246 | 1.041 | 1.353 | 7.0 | 30 | 35 | 40 | |||||
626152! | 10 | 4 | 0.111 | 45 | 60 | 0.633 | 172 | 300 | 1.041 | 1.353 | 7.6 | 24 | 28 | 32 | |||||
621887 | 10 | 7 | 0.111 | 45 | 60 | 0.751 | 272 | 453 | 1.041 | 1.353 | 9.0 | 21 | 25 | 28 | |||||
621883 | 10 | 10 | 0.111 | 45 | 80 | 0.992 | 384 | 669 | 1.041 | 1.353 | 11.9 | 15 | 18 | 20 | |||||
TBA | 10 | 4 | 0.113 | 30 | 60 | 0.566 | 165 | 253 | 1.02 | 1.314 | 6.7 | 24 | 28 | 32 | |||||
TBA | 8 | 3 | 0.142 | 45 | 60 | 0.646 | 197 | 324 | 0.64 | 0.824 | 7.8 | 40 | 50 | 55 | |||||
TBA | 8 | 4 | 0.142 | 45 | 60 | 0.707 | 253 | 383 | 0.64 | 0.824 | 8.5 | 32 | 40 | 44 | |||||
TBA | 6 | 3 | 0.178 | 45 | 60 | 0.72 | 295 | 443 | 0.411 | 0.535 | 8.6 | 55 | 65 | 75 | |||||
624410 | 6 | 4 | 0.178 | 55 | 80 | 0.883 | 387 | 641 | 0.411 | 0.535 | 10.6 | 44 | 52 | 60 | |||||
TBA | 4 | 3 | 0.225 | 45 | 60 | 0.864 | 449 | 661 | 0.258 | 0.336 | 10.4 | 70 | 85 | 95 | |||||
624409 | 2 | 2 | 0.277 | 55 | 80 | 0.962 | 472 | 693 | 0.162 | 0.211 | 11.5 | 95 | 115 | 130 | |||||
TBA | 2 | 3 | 0.283 | 45 | 80 | 0.987 | 689 | 944 | 0.162 | 0.211 | 11.8 | 95 | 115 | 130 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
! Copper drain wire under tape shield
^ UL Listed part number
! Copper drain wire under tape shield