SPEC 45411

2000 Volt Copper Type PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Copper Conductor XLPE Insulation. Sizes 12 AWG through 1000 Kcmil. Heat, Moisture, Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE). Colors available upon request.

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 4703 Standard for Photovoltaic Wire
  • Buy American: Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made 600V products.
  • VW-1 Vertical-Wire Flame Test (Optional)
  • Sample Print Legend:

    SOUTHWIRE E316464 MASTER-DESIGN {UL} PV WIRE XX AWG (XXX.XX{mm2}) CU 2000V 90{D}C WET OR DRY -40{D}C SUN RES DIRECT BURIAL VW-1 OR RHW-2 2000V --- RoHS {MMM/DD/YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    59795812190.087750.2432040
    57996210190.113750.2633253
    5690378190.139850.3135180
    5690396190.174850.34981113
    5690404190.221850.395129167
    5690412190.277850.456205251
    TBA1190.3211050.531258323
    5690431/0190.3601050.57326396
    5690442/0190.4041050.614411489
    TBA3/0190.4541050.664518604
    TBA4/0190.5101050.705653749
    TBA250370.5581200.783772891
    590138350370.6611200.90110811219
    578324500370.7891201.0315441706
    TBA600610.8661351.1218532051
    TBA750610.9681351.26323162534
    TBA1000611.1171351.40230883336
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    597958121.9401.6602.0750.045202020
    579962102.1831.0401.3000.033303030
    56903782.21320.6520.8150.038405055
    56903962.52100.4110.5140.035556575
    56904042.93340.2580.3230.033708595
    56904123.35310.1620.2030.03195115130
    TBA14.06700.1290.1610.032110130145
    5690431/04.38450.1020.1280.031125150170
    5690442/04.710650.0810.1020.030145175195
    TBA3/05.113420.0640.0810.029165200225
    TBA4/05.516930.0510.0640.029195230260
    TBA2506.120000.0430.0550.029215255290
    5901383507.028000.0310.0400.028260310350
    5783245008.040000.0220.0280.027320380430
    TBA6008.848000.0180.0240.027350420475
    TBA7509.760000.0140.0200.027400475535
    TBA100010.980000.0110.0160.026455545615
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).

    Colors and Stock Code

    SizeStock CodeColor
    1/0 (19)677562Green w/ Yellow Stripe

    Revision: 3.0.00C