SPEC 80210
35kV AL 100% TRXLPE Full Neutral Primary UD HI-DRI-PLUS®
Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. Full Copper Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied Full Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- Under short circuit conditions, the maximum allowable shield temperature for crosslinked jackets is 350ºC as opposed to only 200ºC for a PE type of jacket. The higher temperature allows for more fault current capacity, thus reducing the amount of copper required in the neutral design.
- Not recommended for use above 90ºC in wind farm applications
Specifications:
Sample Print Legend:
SOUTHWIRE(R) (UL) HI-DRI-PLUS(R) AWG XX AL 35000 VOLTS TR XLPE INSULATION XX MILS (NESC) MV105 -- SOUTHWIRE (MM/YYYY) NON-CONDUCTING JACKET (PLANT) SEQUENTIAL FOOTAGE MARKS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension* |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
TBA | 1/0 (1) | 0.325 | 1.052 | 345 | 1.152 | 16x14 | 0.164 | 50 | 1.380 | 861 | 16.6 | 634 |
626294 | 1/0 (19) | 0.352 | 1.079 | 345 | 1.179 | 19x16 | 0.164 | 50 | 1.387 | 815 | 16.9 | 634 |
TBA | 1/0 (19) | 0.352 | 1.079 | 345 | 1.179 | 16x14 | 0.164 | 50 | 1.407 | 889 | 16.9 | 634 |
TBA | 2/0 (19) | 0.395 | 1.122 | 345 | 1.222 | 13x12 | 0.128 | 50 | 1.482 | 1029 | 17.8 | 799 |
TBA | 3/0 (19) | 0.443 | 1.170 | 345 | 1.270 | 16x12 | 0.104 | 50 | 1.530 | 1152 | 18.4 | 1007 |
663864 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 24x14 | 0.080 | 50 | 1.556 | 1206 | 12.4 | 1270 |
662826^ | 4/0 (19) | 0.498 | 1.225 | 345 | 1.325 | 20x12 | 0.080 | 50 | 1.629 | 1362 | 19.5 | 1270 |
TBA | 250 (37) | 0.558 | 1.294 | 345 | 1.394 | 16x10 | 0.065 | 80 | 1.758 | 1614 | 21.1 | 1500 |
TBA | 350 (37) | 0.661 | 1.397 | 345 | 1.497 | 16x9 | 0.052 | 80 | 1.886 | 1947 | 22.6 | 2100 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
^ Non-UL listed
^ Non-UL listed
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | A/1000ft | W/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
1/0 (1) | 0.168 | 0.211 | 0.073 | 0.052 | 0.278 | 1.687 | 0.371+j0.078 | 0.213+j0.052 | 6004.7 | 160 | 195 |
1/0 (19) | 0.168 | 0.211 | 0.069 | 0.051 | 0.291 | 1.765 | 0.371+j0.077 | 0.213+j0.051 | 6004.7 | 160 | 195 |
1/0 (19) | 0.168 | 0.211 | 0.069 | 0.051 | 0.291 | 1.765 | 0.371+j0.077 | 0.213+j0.051 | 6004.7 | 160 | 195 |
2/0 (19) | 0.133 | 0.167 | 0.065 | 0.050 | 0.311 | 1.886 | 0.295+j0.063 | 0.170+j0.049 | 7751.5 | 185 | 220 |
3/0 (19) | 0.105 | 0.132 | 0.061 | 0.048 | 0.333 | 2.020 | 0.238+j0.053 | 0.135+j0.047 | 9540.3 | 210 | 250 |
4/0 (19) | 0.0836 | 0.105 | 0.056 | 0.047 | 0.358 | 2.173 | 0.186+j0.045 | 0.109+j0.046 | 12321.7 | 240 | 285 |
4/0 (19) | 0.0836 | 0.105 | 0.056 | 0.047 | 0.358 | 2.173 | 0.186+j0.045 | 0.109+j0.046 | 12321.7 | 240 | 285 |
250 (37) | 0.0707 | 0.089 | 0.052 | 0.046 | 0.390 | 2.363 | 0.156+j0.039 | 0.094+j0.044 | 15165.1 | ||
350 (37) | 0.0505 | 0.064 | 0.046 | 0.044 | 0.436 | 2.643 | 0.117+j0.035 | 0.070+j0.041 | 19124.4 | 315 | 370 |
* Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
† Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension* |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
TBA | 1/0 (1) | 8.25 | 26.72 | 8.76 | 29.26 | 16x14 | 0.54 | 1.27 | 35.05 | 1281 | 421.64 | 2821 |
626294 | 1/0 (19) | 8.94 | 27.41 | 8.76 | 29.95 | 19x16 | 0.54 | 1.27 | 35.23 | 1213 | 429.26 | 2821 |
TBA | 1/0 (19) | 8.94 | 27.41 | 8.76 | 29.95 | 16x14 | 0.54 | 1.27 | 35.74 | 1323 | 429.26 | 2821 |
TBA | 2/0 (19) | 10.03 | 28.50 | 8.76 | 31.04 | 13x12 | 0.42 | 1.27 | 37.64 | 1531 | 452.12 | 3556 |
TBA | 3/0 (19) | 11.25 | 29.72 | 8.76 | 32.26 | 16x12 | 0.34 | 1.27 | 38.86 | 1714 | 467.36 | 4481 |
663864 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 24x14 | 0.26 | 1.27 | 39.52 | 1795 | 314.96 | 5652 |
662826^ | 4/0 (19) | 12.65 | 31.12 | 8.76 | 33.65 | 20x12 | 0.26 | 1.27 | 41.38 | 2027 | 495.30 | 5652 |
TBA | 250 (37) | 14.17 | 32.87 | 8.76 | 35.41 | 16x10 | 0.21 | 2.03 | 44.65 | 2402 | 535.94 | 6675 |
TBA | 350 (37) | 16.79 | 35.48 | 8.76 | 38.02 | 16x9 | 0.17 | 2.03 | 47.90 | 2897 | 574.04 | 9345 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
^ Non-UL listed
^ Non-UL listed
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | A/km | W/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
1/0 (1) | 0.5512 | 0.69 | 0.0223 | 0.1706 | 0.912 | 5.5348 | 0.371+j0.078 | 0.213+j0.052 | 6004.7 | 160 | 195 |
1/0 (19) | 0.5512 | 0.69 | 0.0210 | 0.1673 | 0.955 | 5.7907 | 0.371+j0.077 | 0.213+j0.051 | 6004.7 | 160 | 195 |
1/0 (19) | 0.5512 | 0.69 | 0.0210 | 0.1673 | 0.955 | 5.7907 | 0.371+j0.077 | 0.213+j0.051 | 6004.7 | 160 | 195 |
2/0 (19) | 0.4364 | 0.55 | 0.0198 | 0.1640 | 1.020 | 6.1877 | 0.295+j0.063 | 0.170+j0.049 | 7751.5 | 185 | 220 |
3/0 (19) | 0.3445 | 0.43 | 0.0186 | 0.1575 | 1.093 | 6.6273 | 0.238+j0.053 | 0.135+j0.047 | 9540.3 | 210 | 250 |
4/0 (19) | 0.2743 | 0.34 | 0.0171 | 0.1542 | 1.175 | 7.1293 | 0.186+j0.045 | 0.109+j0.046 | 12321.7 | 240 | 285 |
4/0 (19) | 0.2743 | 0.34 | 0.0171 | 0.1542 | 1.175 | 7.1293 | 0.186+j0.045 | 0.109+j0.046 | 12321.7 | 240 | 285 |
250 (37) | 0.2320 | 0.29 | 0.0158 | 0.1509 | 1.280 | 7.7526 | 0.156+j0.039 | 0.094+j0.044 | 15165.1 | ||
350 (37) | 0.1657 | 0.21 | 0.0140 | 0.1444 | 1.430 | 8.6713 | 0.117+j0.035 | 0.070+j0.041 | 19124.4 | 315 | 370 |
* Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
† Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
Revision: 3.0.00C