SPEC 44101
2/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved
Flexible Copper Conductors, Ethylene Propylene Diene Monomer (EPDM) Insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Construction:
- Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
- Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
- Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white
- Fillers:Paper fillers applied as needed to round the cable core
- Reinforcement Binder:Reinforcing binder with twine applied over the core
- Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)
Applications and Features:
Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-1 and FT-5 Flame Tests. cUL listing on select items only.
Specifications:
Sample Print Legend:
# AWG 2/C TYPE W PORTABLE POWER CABLE 90°C WET OR DRY 2000V OIL AND SUN RES (UL) P-136-35-MSHA AIWTM c(UL) FT1/FT5 (-40°C)
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | No. | inch | mil | inch | inch | lb/1000ft | |
559272 | 8 | 2 | 71 | 0.148 | 60 | 0.3 | 0.84 | 320 |
TBA | 6 | 2 | 65 | 0.184 | 60 | 0.33 | 0.91 | 410 |
570254 | 4 | 2 | 112 | 0.235 | 60 | 0.39 | 1.01 | 550 |
TBA | 2 | 2 | 168 | 0.315 | 60 | 0.47 | 1.24 | 840 |
TBA | 1 | 2 | 224 | 0.362 | 80 | 0.55 | 1.44 | 1130 |
TBA | 1/0 | 2 | 259 | 0.385 | 80 | 0.58 | 1.49 | 1260 |
559276 | 2/0 | 2 | 324 | 0.42 | 80 | 0.61 | 1.56 | 1490 |
TBA | 3/0 | 2 | 418 | 0.47 | 80 | 0.66 | 1.66 | 1780 |
TBA | 4/0 | 2 | 532 | 0.535 | 80 | 0.73 | 1.82 | 2180 |
TBA | 250 | 2 | 608 | 0.605 | 95 | 0.83 | 1.99 | 2510 |
TBA | 350 | 2 | 855 | 0.67 | 95 | 0.89 | 2.15 | 3280 |
TBA | 500 | 2 | 1221 | 0.858 | 95 | 1.08 | 2.59 | 4620 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity In Air 60°C† | Allowable Ampacity In Air 75°C† | Allowable Ampacity In Air 90°C† |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |
559272 | 8 | 2 | 0.65 | 0.82 | 5 | 55 | 65 | 74 |
TBA | 6 | 2 | 0.42 | 0.52 | 5 | 72 | 88 | 99 |
570254 | 4 | 2 | 0.26 | 0.33 | 6 | 96 | 115 | 130 |
TBA | 2 | 2 | 0.17 | 0.21 | 7 | 128 | 152 | 174 |
TBA | 1 | 2 | 0.13 | 0.16 | 9 | 150 | 178 | 202 |
TBA | 1/0 | 2 | 0.11 | 0.13 | 9 | 173 | 207 | 234 |
559276 | 2/0 | 2 | 0.08 | 0.1 | 9 | 199 | 238 | 271 |
TBA | 3/0 | 2 | 0.07 | 0.08 | 10 | 230 | 275 | 313 |
TBA | 4/0 | 2 | 0.05 | 0.07 | 11 | 265 | 317 | 361 |
TBA | 250 | 2 | 0.04 | 0.06 | 12 | 296 | 354 | 402 |
TBA | 350 | 2 | 0.03 | 0.04 | 13 | 363 | 435 | 495 |
TBA | 500 | 2 | 0.02 | 0.03 | 16 | 448 | 537 | 613 |
† Ampacity based on NEC 400.5(A)(2) and is for a two-conductor W cable only where the individual conductors are not installed in raceways and are not in physical contact with each other except in lengths not to exceed 600 mm (24 in.) where passing through the wall of an enclosure.
Revision: 3.0.00M