SPEC 44102

3/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, green.
  4. Fillers:Paper fillers applied as needed to round the cable core
  5. Reinforcement Binder:Reinforcing binder with twine applied over the core
  6. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per Article NEC 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as perminant building wiring. Meets FT-5 Flame Test. cUL listing on select items only.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    # AWG 3/C TYPE W PORTABLE POWER CABLE 90°C WET OR DRY 2000V OIL AND SUN RES (UL) P-136-35-MSHA AIWTM c(UL) FT1/FT5 (-40°C)
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessDiameter Over InsulationApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilinchinchlb/1000ft
    55815183710.148600.30.95470
    57025663650.184600.331.03600
    571409431120.235600.391.11790
    559279231680.315600.471.311130
    TBA132240.362800.551.51490
    TBA1/032590.385800.581.581,730
    5592802/033240.42800.611.652,050
    6464683/034180.470800.661.762,480
    5702524/035320.535800.731.933,040
    TBA25036080.605950.832.293,870
    57129235038550.67950.892.434,950
    599101500312210.858951.0542.896,534
    571442500312210.858951.082.896,900
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°C†Allowable Ampacity In Air 75°C†Allowable Ampacity In Air 90°C†
    AWG/KcmilNo.Ω/1000ftΩ/1000ftMΩ/1000ftinchAmpAmpAmp
    558151830.6660.8480.0416485765
    570256630.4150.5290.0386637787
    571409430.2630.3350.036784101114
    559279230.1720.2150.0348112133152
    TBA130.1310.1660.0349131156177
    TBA1/030.1090.1390.0349151181205
    5592802/030.08340.1060.03310174208237
    6464683/030.06620.08400.03211201241274
    5702524/030.05250.0660.03212232277316
    TBA25030.04480.0580.03214259310352
    57129235030.0320.0410.03115318381433
    59910150030.02240.0290.0317392470536
    57144250030.02240.0290.0317392470536
    * Inductive reactance based three current-carrying conductors.
    † Ampacity based on NEC 400.5(A)(2) and is for a single isolated cable in air operated at an ambient temperature of 30°C connected to utilization equipment with three current-carrying conductors.

    Revision: 3.0.00M