SPEC 47801

3/C CU 5KV 100% & 133% EPR/CPE RHINOPOWERTM Type MP-GC. MSHA Approved

Class B Cu Conductors, Ethylene Propylene Rubber (EPR) 100% & 133% Insulation Level, Cu Tape Shield, Chlorinated Polyethylene (CPE) Jacket w/ Optional Reflective Stripes, 90°C

...

Construction:

  1. Conductor:Class B compact stranded bare copper per ASTM B3 and ASTM B496
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:Ethylene Propylene Rubber (EPR) 100% and 133% Insulation Level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Grounding Conductors:Two Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  7. Ground Check:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 with yellow high strength, polypropylene insulation
  8. Filler:Rubber Fillers as needed
  9. Reinforcement:Tape and Reinforcing twine applied over the core for improved mechanical integrity and ease of stripping
  10. Jacket:Black, mold cured, single layer, flame resistant, thermosetting Chlorinated Polyethylene (CPE). Alternate jacket colors available
  11. Reflective Stripe:Highly visible reflective stripe embedded into the outer jacket to increase safety and help prevent cable runover (optional, contact your sales representative for part number)

Applications and Features:

RHINOPOWERTM Type MP-GC mine power feeder cable is a heavy-duty power cable for use in stationary horizontal HV mine power distribution circuits, for permanent or semi-portable applications with power transmission in deep mines, surface mines, open pits, tunnels, in conduit or duct (not to exceed max rated voltage), and suitable for direct burial in wet or dry locations. For vertical drop requirements consult with factory application specialist.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B496 Compact Round Concentric-lay-standard copper
  • ICEA S-75-381 Portable and Power Feeder Cables for Use in Mines
  • MSHA Approved
  • Sample Print Legend:

    SOUTHWIRE (R) RHINOTM BRAND CABLE # AWG 3/C COMPACT CU TYPE MP-GC 5000V 100% OR 133% INS. LEVEL P-07-K140017 MSHA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGround SizeGround StrandsGround Check SizeGround Check StrandsGround Check Insulation ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilinchAWGNo.AWGNo.milmilinchlb/1000ft
    TBA6370.169900.385107107301101.21950
    TBA4370.213900.4298787451101.321250
    TBA2370.268900.4846787451101.451660
    TBA13190.299900.5155787451101.531940
    TBA1/03190.336900.5524787451101.632290
    578410012/03190.376900.5923787451101.742730
    586912993/03190.423900.6392787451401.883290
    TBA4/03190.475900.69111987451402.003930
    587013992503370.52900.7361/01987451402.134580
    TBA3003370.57900.7861/01987451402.255190
    TBA3503370.616900.8322/01987451402.355940
    TBA4003370.659900.8753/01987451402.456740
    TBA4503370.7900.9163/01987451402.557340
    TBA5003370.736900.9524/01987451402.648180
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberDC Resistance @ 25°CAC Resistance @ 90°CCapacitive ReactanceInductive ReactanceWorking TensionMin Bending RadiusAllowable Ampacity In Air 90°C†
    AWG/KcmilNo.Ω/1000ftΩ/1000ftMΩ*1000ftMΩ/1000ftlbinchAmp
    TBA630.4170.5210.0440.044179.00014.593
    TBA430.2620.3280.0380.041285.00015.8122
    TBA230.1640.2050.0320.038454.00017.4159
    TBA130.1300.1630.0290.037572.00018.4184
    TBA1/030.1040.1300.0270.035722.00019.6211
    578410012/030.0820.1030.0240.034910.00020.9243
    586912993/030.0650.0810.0220.0331147.00022.6279
    TBA4/030.0520.0650.0200.0321446.00024321
    5870139925030.0440.0550.0190.0311709.00025.6355
    TBA30030.0370.0460.0170.0312051.00027398
    TBA35030.0310.0390.0160.0302393.00028.2435
    TBA40030.0270.0340.0150.0302734.00029.4470
    TBA45030.0240.0300.0150.0293075.00030.6502
    TBA50030.0220.0280.0140.0293418.00031.7539
    † Ampacity based on ICEA S-75-381 Table I-1 and is for a single isolated cable in air operated with an open-circuited shield at an ambient temperature of 40°C and a conductor temperature of 90°C

    Revision: 3.0.00M